2.5 Hp Low Temp Condensing Unit
video
2.5 Hp Low Temp Condensing Unit

2.5 Hp Low Temp Condensing Unit

The product may have some questions during use, and we have compiled some precautions for 2.5 hp low temp condensing unit use to guide customers in their usage and installation.

The product may have some questions during use, and we have compiled some precautions for 2.5 hp low temp condensing unit use to guide customers in their usage and installation.

 

What should be noted when adding refrigerant?

 

(1) Fill refrigerant from the high-pressure side after vacuuming.

(2) If the refrigerant is insufficient, charge gaseous refrigerant from the low-pressure side during system operation. If the system lacks refrigerant, the temperature switch or compressor motor thermostat will automatically reset. After 15 minutes of refrigerant charging, the system must run for at least 1 minute.

(3) Add refrigerant until there are no bubbles in the observation window, and it should not exceed the maximum amount. When the refrigerant charge is large, a receiver is required.

(4) The evaporator must be within the maximum refrigerant range. If the refrigerant charge of R404A is insufficient, then the liquid injection amount is insufficient; If overcharged, the oil will be diluted, causing damage to the sliding surface and compression of the liquid. In order to charge correctly, it is necessary to use a mirror for confirmation.

 

What Should be Pay Attention To When Electric Wiring?

 

(1) Please use a dedicated circuit! (Do not share with other products)

(2) Please install the grounding wire!

(3) Please install a leakage protector (leakage relay cannot protect)

(4) Do not allow wires to come into contact with high-temperature components (compressors, condensers, discharge pipes) and metal edges.

 

Condensing Unit Model

GF-HS10EL

GF-HS15EL

GF-HS20EL

GF-HS25EL

GF-HS30EL

GF-HS20FL

GF-HS30FL

 

Rated Power(W)

800

1120

1980

2350

2680

1980

2680

 

Power Capacity (HP)

1HP

1.5HP

2HP

2.5HP

3HP

2HP

3HP

 

Power Supply

220V/50Hz

380V/50Hz

 

Refrigerant (Max/kg)

R404A(1.2)

R404A(1.4)

R404A(3.0)

 

Start-up Current (A)

25

37

50

50

60

27

27

 

Maximum Working Current(A)

4.3

6.5

8.6

9.5

12.7

3.2

4.7

 

Evaporating Temp Range(°C)

-45〜-5

 

Ambient Temp Range(°C)

-7〜43

 

Compressor Model

C-RHN75E4A

C-RHN110E4A

C-3RH322L4AAL

C-3RH322L4AAL

C-3RH463L4AAL

C-RHN153L8A

C-RHN223L8A

 

Pressure Controller

P830HM

 

Accumulator Volume (L)

0.8

 

Gas-liquid Separator Volume (L)

0.65

1.2

 

Condenser

Spec (R*R*L mm)

4*4.5*540

5*4.5*630

5*4.5*900

5*4.5*995

6*4.5*1060

5*4.5*900

6*4.5*1060

 

Fan Motor

Motor Output Power/Qty(W)

16*2

16*2

16*3

16*3

16*3

16*3

16*3

 

Fan Diameter

(mm)

Φ230*2

Φ230*2

Φ230*3

Φ230*3

Φ230*3

Φ230*3

Φ230*3

 

Air volume(m³/hr)

820*2

820*2

820*3

820*3

820*3

820*3

820*3

 

Pipe
(mm)(inch)

Suction OD

12.7(1/2'')

 

Liquid Outlet OD

9.53(3/8'')

 

External
Dimension(mm)

L ± 2

680

790

1050

1145

1210

1050

1210

 

W ± 2

485

485

540

540

570

540

570

 

H ± 4

261

261

263

263

263

263

263

 

Pitch of holes Φ9--L*W(mm*mm)

660*465

770*465

1030*520

1125*520

1190*550

1030*520

1190*550

 

Cooling
Capacity(W)

Evap Temp (°C)

Ambient Temperature 32°C

 

-40

505

840

1260

1425

1620

1260

1620

 

-35

655

1090

1580

1790

2080

1580

2080

 

-30

810

1190

1890

2140

2630

1890

2630

 

-25

975

1545

2310

2615

3320

2310

3320

 

-20

1190

1865

2730

3090

3955

2730

3955

 

-15

1430

2100

3095

3505

4540

3095

4540

 

-10

1795

2426

3680

4170

5485

3680

5485

 

-5

2135

2790

4100

4645

6485

4100

6485

 

Wiring

Leakage
Protector

Rated current(A)

10

15

25

25

30

10

15

 

Action
Current(mA)

30

 

Wire Dia
(m²)

10m

2.0

2.0

4.0

4.0

5.0

2.0

2.0

 

20m

2.0

3.5

6.0

6.0

6.0

2.0

3.5

 

30m

3.5

3.5

6.0

6.0

6.0

3.5

3.5

 
                     

Code

Test
Condition

Ambient Temp(°C)


Suction
Temp(°C)

Evap Temp
(°C)

Test Power Supply

 

Standard

32.2

5

-23.3

1PH 50Hz 220V/3PH 50HZ 380V

 

Maximum

43

5

-23.3

1PH 50Hz 220V/3PH 50HZ 380V

 
                     

1. The refrigerant filling amount should be controlled as much as possible, and should not exceed the values in the table at most

2. The diameter of the suction pipe and evaporator should be determined after considering the return oil and confirming the gas flow rate again

3. When selecting the diameter of the connecting pipeline, special attention should be paid to ensuring that the gas flow velocity reaches 3.8m/s or more in the horizontal pipe and 7.6m/s or more in the vertical pipe

4. The length of the single-sided pipe should be below 10 meters, and the height difference should be below 3 meters at this time

Hot Tags: 2.5 hp low temp condensing unit, China 2.5 hp low temp condensing unit manufacturers, suppliers, factory, condensing machinery for refrigeration, Monoblock Refrigeration Unit, Cooler Evaporator Unit, Monoblock Refrigeration Unit With Compressor, Water Cooled Condenser Coil, Universal Evaporator Coil